| Parameter | Value |
| Manufacturer | Schneider Electric |
| Product Line | Modicon Quantum Automation Platform |
| Input Channels | 16 Analogue Inputs |
| Input Type | Differential |
| Analogue Input Resolution | 16 bits |
| Linear Measuring Range (Voltage) | 1...5 V, 0...10 V, +/-10 V |
| Linear Measuring Range (Current) | 4...20 mA, 0...20 mA |
| Absolute Maximum Input (Voltage) | 50 V DC |
| Absolute Maximum Input (Current) | 25 mA |
| Input Impedance (Current) | 250 Ohm (+/- 0.01 %) |
| Input Impedance (Voltage) | > 20 MOhm |
| Type of Filter | Single pole low pass |
| Filter Cut-off Frequency | -3 dB at 15 Hz (+/- 20 %) |
| Absolute Accuracy Error | +/- 0.05 % of full scale (typical) |
| +/- 0.1 % of full scale (maximum) | |
| Linearity Error | +/- 0.04 % |
| Accuracy Drift (Temperature) | +/- 0.0025 % of full scale/°C (typical) |
| <= 0.005 % of full scale/°C (maximum) | |
| Common Mode Rejection | > -72 dB at 60 Hz |
| Isolation (Channels to Bus) | 1000 V DC (3000 V DC for 60 s) |
| Isolation (Between Channels) | 30 V DC |
| Update Time | 5 ms |
| Fault Detection | Broken wire (4-20 mA), Undervoltage (Voltage ranges) |
| Addressing Requirement | 17 input words |