Schneider Electric BMXAMI0810 Modicon X80 Isolated Analog Input Module — 8‑Channel, 0–20mA / 4–20mA / ±10V, 15‑bit + sign, 300V Channel Isolation, IP20
Schneider Electric BMXAMI0810 Modicon X80 Isolated Analog Input Module — 8‑Channel, 0–20mA / 4–20mA / ±10V, 15‑bit + sign, 300V Channel Isolation, IP20
Precio habitual
$360.00 USD
Precio habitual
Precio de oferta
$360.00 USD
Los gastos de envío se calculan en la pantalla de pago.
Cantidad
No se pudo cargar la disponibilidad de retiro
Secure checkout via Stripe & PayPal
Product overview The Schneider Electric BMXAMI0810 is an isolated high‑level analog input module in the Modicon X80 family. It provides eight independent, isolated analog inputs with 15‑bit plus sign resolution and flexible input ranges to interface directly with a wide variety of transmitters and sensors used in continuous process control.
Key specifications
- Manufacturer: Schneider Electric
- Model: BMXAMI0810 (Modicon X80 analog input module)
- Function: Isolated analog input module, 8 channels
- Supported input ranges (per channel):
- Current: ±20 mA, 0…20 mA, 4…20 mA
- Voltage: ±10 V, ±5 V, 0…10 V, 0…5 V, 1…5 V
- Conversion & resolution:
- ADC: 16‑bit conversion (user resolution 15 bits + sign)
- Measurement resolution: 1.4 µA for current ranges; 0.36 mV for voltage ranges
- Measurement error (0…60 °C): ≤ 0.3 % FS for current ranges; ≤ 0.1 % FS for voltage ranges
- Typical accuracy at 25 °C: 0.15 % FS (current), 0.075 % FS (voltage)
- Temperature drift: 50 ppm/°C (current ranges); 30 ppm/°C (voltage ranges)
- Isolation:
- 300 V DC between channels
- 1400 V DC between channels and ground
- 1400 V DC between channels and bus
- Input conditioning & protection:
- Input impedance: 10 MΩ (voltage mode); 250 Ω + 3.6…50 Ω internal protective resistor (current mode)
- Permitted overloads: up to ±30 V on voltage ranges; up to ±30 mA on current ranges
- Precision of internal conversion resistor: 0.1 % (15 ppm/°C)
- Minimum crosstalk attenuation: 80 dB; common mode rejection: 80 dB
- Performance & timing:
- Fast read cycle time: 1 ms + 1 ms × number of channels used
- Nominal read cycle time: 9 ms for 8 channels
- Diagnostics & signalling:
- LEDs: RUN (green), 1 per‑channel diagnostic LED (green), ERR (red), I/O (red)
- Internal recalibration: yes (automatic/internal)
- Mechanical & electrical:
- Electrical connection: 28‑way removable terminal block
- Net weight: 0.165 kg
- Module occupies 1 rack slot; IP20 enclosure rating
- MTBF: 900,000 hours
- Power consumption:
- Typical: 1.06 W at 24 V DC; Maximum: 1.50 W at 24 V DC
- Current consumption: 54 mA at 24 V DC; 150 mA at 3.3 V DC
- Environmental:
- Operating ambient temperature: 0…60 °C
- Storage temperature: −40…85 °C
- Relative humidity: 5…95 % at 55 °C without condensation
- Vibration / shock: 3 gn / 30 gn
- Operating altitude: 0…2000 m (2000…5000 m with derating)
- Certifications & standards:
- CE, RCM, CSA, EAC, UL, Merchant Navy
- Standards: IEC 61131‑2, IEC 61010‑2‑201, UL 61010‑2‑201, CSA C22.2 No 61010‑2‑201
- Firmware & documentation:
- Firmware: BMXAMI0810 firmware SV01.80 (or earlier as supported)
- Documentation: product datasheet, user guide, instruction sheet, CAD available from Schneider Electric portal
- Packaging & warranty:
- Packaging and weight per Schneider Electric data; contractual warranty: 18 months
Features & benefits
- Eight configurable isolated channels allow mixed current/voltage inputs per channel for maximum installation flexibility.
- Genuine channel isolation (300 V) and high isolation to ground/bus (1400 V) reduce ground‑loop errors and increase measurement safety.
- High resolution and low drift deliver accurate process values for control loops and monitoring.
- Per‑channel diagnostics and status LEDs simplify commissioning and fault finding.
- Compact Modicon X80 form factor and removable 28‑way terminal block speed wiring and maintenance.
Applications
- Process industries, water/wastewater, chemical plants, utilities, manufacturing and other applications requiring multi‑channel isolated analog acquisition for closed‑loop control and monitoring.
Installation and service notes
- Wire sensors/transmitters to the 28‑way removable terminal block following Schneider Electric wiring diagrams. Verify per‑channel range selection prior to commissioning.
- Respect isolation ratings when planning grounding and bus wiring. Install in IP20‑rated cabinets and follow ambient/humidity limits.
- Consult datasheet for wiring details, range configuration, filtering, shielding and firmware compatibility (SV01.80). Internal recalibration removes need for external recalibration procedures.
Share