Autronica BD-200 Heat Detector — Interactive Plug‑in Point Heat Detector (BDH-200)

Overview

  • Manufacturer: Autronica Fire and Security AS
  • Model: BD-200 (detector head 116-BDH-200)
  • Type: Point heat detector (thermistor-based) for interactive fire detection systems
  • Intended use: Dry-area heat detection where smoke detectors may give unwanted alarms (kitchens, galleys, bathrooms, boiler rooms, workshops, etc.)
  • Standards: EN 54-5 / EN 54-17 (see manufacturer for full approvals and certificates)

Key features

  • Interactive plug‑in detector head compatible with Autronica bases and interactive panels.
  • Configurable alarm classes: A1, A1R (rate-of-rise), A2S (slow), B, C — selectable to suit the application environment.
  • Thermistor temperature measurement provides temperature readout at the detector point.
  • Built‑in short‑circuit isolator in each detector.
  • Built‑in alarm LED; supports external LED output (requires specified varistor per datasheet).
  • Automatic addressing for Autronica interactive systems.
  • Proven technology, EMC compliant and designed to meet major maritime classification society requirements.
  • Low susceptibility to dust, humidity, exhaust gases and electromagnetic disturbance.

Technical specifications (as per datasheet)

  • Supply voltage: 10–27 VDC
  • Current consumption: Standby < 0.3 mA; External alarm indicator 6 mA
  • Weight: 140 g
  • Materials: PC/ABS (light grey)
  • Degree of protection: IP44D
  • Operating temperature: –20 °C to +80 °C
  • Storage temperature: –55 °C to +80 °C
  • Humidity (non‑condensing): Max. 95% RH
  • CPD certificate: 1134-CPD-018
  • Maintenance: None (service: replace if faulty)
  • Maximum application / sensitivity: Refer to detector class table below (use appropriate class selection for installation)

Detector class performance (use for configuration & siting)

  • A1: Typical application temp 25 °C — Maximum application temp 50 °C — Min static response 54 °C — Max static response 65 °C
  • A1R (rate‑of‑rise): Typical 5 °C — Maximum application temp 50 °C — Min static response 54 °C — Max static response 65 °C
  • A2S (slow): Typical 25 °C — Maximum application temp 50 °C — Min static response 54 °C — Max static response 70 °C
  • B: Typical 40 °C — Maximum application temp 65 °C — Min static response 69 °C — Max static response 85 °C
  • C: Typical 55 °C — Maximum application temp 80 °C — Min static response 84 °C — Max static response 100 °C

Mechanical & electrical notes

  • Detector base part number: 116-BWA-100. Optional conduit boxes: 116-BWP-100/20 (M20) and 116-BWP-100/25 (M25). Optional audible indicator: 116-BBR-52 SmartBuzzer.
  • Pinout (base): 1 = in, 2 = out, 3 = common (+ in, + out), 4 = external LED. External LED connection: LED between terminals 3 (+) and 4; when using LED or other equipment on terminal 4, install varistor Siemens SIOVS07K25 (39V) — Autronica part no. 116-8464-003.5039 — between terminals 1 and 4 in the base.

Applications

  • Ideal for environments prone to false smoke alarms (kitchens, galleys, boiler rooms, workshops). Suitable for industrial, maritime and offshore installations when used within an Autronica interactive fire detection system.

Ordering & identification

  • Product: Autronica BD-200 Heat Detector (detector head 116-BDH-200)
  • Datasheet ref: 116-P-BD200/CGB, Rev. D, 2009-06-23
Vollständige Details anzeigen